IEC 61008-1:2024, Clause 1 is applicable except for the first paragraph, which is replaced by the first paragraph below, and the last paragraph, which is replaced by the second paragraph and note below:
This document applies to residual current operated circuit-breakers, without integral overcurrent protection, for household and similar uses (hereafter referred to as RCCBs), classified according to IEC 61008-1:2024, 4.1.2, 4.1.3, 4.1.4, 4.1.5 and 4.1.6. RCCBs according to this document are intended for voltages not exceeding 440 V AC with frequencies of 50 Hz, 60 Hz or 50/60 Hz and currents not exceeding 125 A, intended principally for protection against shock hazard.
This document applies in conjunction with IEC 61008-1:2024. It specifies requirements, tests and test sequences to verify compliance and is used for certification purposes.
NOTE Devices according to this part are not permitted in: DE